* 0.5 MH is a typical starting point for the Common Mode Line Filters. By increasing or decreasing the value of L
you can set the drain current to a minimum to meet your requirements.
Driver to Motor Cable AWG Table
1 Amp (Peak) 5 Amp (Peak)
Length (Feet) 10 25 50 75 100 Length (Feet) 10 25 50 75 100
20 20 18 18 16
16 16 14 12 12
2 Amp (Peak) 6 Amp (Peak)
Length (Feet) 10 25 50 75 100 Length (Feet) 10 25 50 75 100
20 18 16 14 14
14 14 14 12 12
3 Amp (Peak) 7 Amp (Peak)
Length (Feet) 10 25 50 75 100 Length (Feet) 10 25 50 75 100
18 16 14 12 12
12 12 12 12 12
4 Amp (Peak)
Length (Feet) 10 25 50 75 100
18 16 14 12 12
Driver to Motor Supply Cable Wire Size
NOTE: These recommendations will provide optimal protection against EMI and RFI. The actual cable type, wire
gauge, shield type and filtering devices used are dependent on the customer’s application and system.
NOTE: Always use Shielded/Twisted Pairs for the Driver DC Supply Cable, the AC Supply Cable and the Driver to
Motor Cable.